INSTALLATION
Page 20 User guide ref. 9015909-03 Industrial router IPL-E
The other interface (2 or 4 RJ45 depending on versions) are made to
connect to a local area network or directly to the industrial devices.
5 RS232 interface
The RS232 data rate can be tuned from 1200 to 115200 b/s with parity
(even / odd) or no parity.
The data terminal must be less than 10 meters far from the modem.
Cables can be provided to connect the product to DTE and DCE as
follows :
RS232 cables (L=1m)
Code User connector Cable function
CAB592 SubD 9 male To connect a DCE to the IPL-E
CAB593 SubD 9 female To connect a DTE to the IPL-E
CAB609 wires To connect a device providing a specific
connector
6 RS485 interface
The RS485 serial interface is
provided on the front panel 2 pins
screw-block.
Polarisation resistors
1 Kohm bus polarisation resistors
are included inside the product.
RS485 line matching
For a several meters long connection over the RS485 local interface, it is
not necessary to adapt the RS485 line.
For a longer distance, matching and polarisation resistors must be
added.
RS485
+
-
B(+)
A(-)
1 KOhm
1 KOhm
IPL-E