ETIC 1230 Manual do Utilizador Página 46

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 64
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 45
HTML SET UP & DIAGNOSTIC
To configure the Modbus server gateway,
select the modbus menu and then modbus server,
enable the modbus server gateway and set the parameters as follows:
“Modbus protocol” parameter :
Select the RTU or ASCII option
“Activate Proxi cache” parameter :
Enable the proxi option if you wish to avoid to frequent requests on the
serial interface.
“Cache refreshment period” parameter :
the same request is received twice or more inside that delay, it will be
sent only once to the slave on the serial interface.
“Timeout waiting for the answer” parameter :
Set up the timeout the gateway has to wait for the answer of the modbus
slave.
“Local retry” parameter :
Set up the number of times the gateway will repeat a request to one of the
modbus slaves on the serial interface before declaring a failure.
“Inter-character gap” parameter :
Set up the maximum delay the gateway will have to wait between a
Page 46 User’s guide ref 9014709-02 XSLAN SHDSL switch
Vista de página 45
1 2 ... 41 42 43 44 45 46 47 48 49 50 51 ... 63 64

Comentários a estes Manuais

Sem comentários